How to size a chiller for a cold plunge, with the arithmetic

November 13, 2026 · 5 min read

Most chiller enquiries arrive as a tub size. 250 litres, 400 litres, 700 litres, and a target temperature. Volume is the easiest thing to measure, so it becomes the number everyone quotes — but on its own it tells you almost nothing about whether the unit will hold 4 °C on the third bather in August, or drift to 9 °C by lunchtime.

Four numbers decide the chiller. Only one of them is volume.

The four numbers

  1. Water volume — litres, measured or calculated from internal dimensions. Not the external footprint.
  2. Pull-down delta — the gap between the water temperature at fill and your target. Mains water in southern China in summer arrives at 30–32 °C; in northern Europe in winter it can arrive at 8 °C. Same tub, same chiller, wildly different first-hour performance.
  3. Pull-down window — how long you are willing to wait between filling and the first plunge. This is a commercial decision, not a technical one. A showroom wants 3 hours. A villa with a 24-hour fill cycle does not care.
  4. Standing heat load — what the tub gains every hour while sitting there. Ambient air, insulation, lid, pump heat, sunshine, bathers.

The arithmetic

Removing heat from water is not complicated. The energy you have to pull out is:

kWh = litres × ΔT × 4.186 ÷ 3600

That is the whole calculation for pull-down. Divide by the hours you are willing to wait and you have the average heat removal rate the chiller has to deliver, in kW.

A worked example from the bench

We ran this on a 250 litre tub, filled to 35 °C, pulled to 3.5 °C and timed. It took 3 hours 07 minutes on a 220–240 V / 50 Hz unit running R32.

Step Value
Water volume 250 L
Start → target 35.0 → 3.5 °C (ΔT = 31.5 K)
Energy to remove 250 × 31.5 × 4.186 ÷ 3600 = 9.16 kWh
Measured time 3 h 07 min (3.12 h)
Average heat removal 9.16 ÷ 3.12 = 2.94 kW
Chiller class we quote for this 3.5 kW nominal

The point of the example is not the 3 hours. It is that the measured rate (2.94 kW) sits comfortably inside a 3.5 kW nominal unit, which leaves headroom for the standing load while the tub is in use. A chiller sized to exactly the pull-down figure will hold temperature badly, because from the moment the fill is done it is no longer working on a closed, insulated box — it is working on a tub with a lid that gets opened.

Why “1 HP per 100 litres” fails

This rule circulates widely and it is not wrong often enough to die, but it is wrong often enough to cost people money. Two 400 litre tubs can need different chillers by a factor of two:

The rule of thumb encodes the first case and gets applied to the second.

Standing load: the part that never sleeps

Load source What drives it What actually reduces it
Lid conduction Lid thickness and fit; a loose lid is an open window Insulated lid with a gasket, not a plank
Wall conduction Timber thickness, any foam or foil layer Insulated jacket, or accept the loss and size for it
Open surface Evaporation and convection. Roughly 0.5–1 kW on a 1.2 m² surface at 27 K below ambient Keep the lid on when not in use; this is the single biggest lever
Pump and pipe heat Every watt the pump draws ends up in the water Right-size the pump; insulate the return line
Bathers Roughly 100–200 W per person in cold water Nothing. Budget for it
Solar gain Dark timber in direct sun Shade, light colour, or a cover

In practice, the uncovered-surface row dominates everything else. A tub quoted around a 3.5 kW chiller will hold 4 °C all day with the lid on, and can lose 3–4 K over two hours of continuous open use on a hot day. That is normal. It is also why “recovery time” is a better question than “pull-down time” once the tub is in service.

Scaling the measurement

The table below takes the measured 2.94 kW and scales it by volume, holding ΔT at 31.5 K and ignoring standing load. It is a planning aid, not a specification — but it is the fastest way to see when a single chiller stops being the right answer.

Volume Energy to remove Time at 2.94 kW To hold ~3 h you need
250 L 9.2 kWh 3.1 h 3.5 kW class
400 L 14.7 kWh 5.0 h 5 kW class
700 L 25.7 kWh 8.7 h 8.5 kW class
1,000 L 36.6 kWh 12.5 h 12 kW class — usually two units

At the 700 litre mark and above, most projects stop buying a bigger chiller and start buying two smaller ones. Two units give redundancy, and a failed compressor becomes a service call instead of a drained tub.

What to send instead of a volume

With those eight lines we can size the chiller and tell you the pull-down time before you commit to a mould, a container, or a price list. Send them through the RFQ form and we will come back with the arithmetic, not just a model number.